10 Key Technical Parameters and Selection Methods for Dry-Type Transformers

10 Key Technical Parameters and Selection Methods for Dry-Type Transformers

In industrial power distribution, building power supply, and new energy projects, dry-type transformers are widely used in indoor substations, data centers, rail transit systems, hospitals, and large industrial facilities due to their high fire-safety ratings, low maintenance requirements, and safe, reliable operation.

1

Compared to oil-immersed transformers, dry-type transformers utilize a solid insulation structure and do not require insulating oil for cooling or insulation; consequently, they pose no risk of oil leakage, offering distinct advantages for use in densely populated areas and locations with stringent fire safety requirements.
However, in practical engineering applications, the selection of a dry-type transformer is not determined solely by capacity. Parameters such as rated voltage, connection group, impedance voltage, loss levels, temperature rise, cooling method, and insulation class all influence the equipment’s operational performance and service life.
For instance, even among 2000 kVA dry-type transformers, differences in core materials, winding structures, and insulation systems employed by various manufacturers result in variations regarding no-load loss, load loss, temperature rise, and short-circuit withstand capability.
Therefore, during the equipment procurement and engineering design phases, it is essential to comprehensively evaluate key technical parameters based on the actual operating environment and load characteristics.

0

I. Number of Phases and Rated Frequency

1.Selection of Number of Phases
Dry-type transformers are primarily classified into two types based on the number of phases: single-phase and three-phase.

TypeCharacteristicsMain Applications
Single-phase TransformerSmall capacity, simple structureLighting systems and small equipment power supply
Three-phase TransformerLarge transmission capacity, high operating efficiencyIndustrial power distribution and building power supply

At present, three-phase dry-type transformers are the most widely used solution in industrial projects and building distribution systems.

For example, when a 10kV distribution system is stepped down to 0.4kV, the commonly used transformers include:

ModelCapacityVoltage Rating
SCB13-1000/101000kVA10/0.4kV
SCB13-1600/101600kVA10/0.4kV
SCB13-2000/102000kVA10/0.4kV
SCB13-2500/102500kVA10/0.4kV

2.Rated frequency

Rated Frequency

The rated frequency refers to the power system frequency corresponding to the designed operating conditions of the transformer.

Power system frequencies vary among different countries and regions:

Country/RegionGrid Frequency
China50Hz
Saudi Arabia60Hz
United Arab Emirates50Hz
Most European countries50Hz
United States60Hz

Note: Some Middle Eastern countries operate on 60Hz power systems. Therefore, transformers for export projects must be designed according to the local grid standards.

If the transformer frequency does not match the power system frequency, it will affect the magnetic flux density, losses, and temperature rise.

The main impacts are as follows:

ItemImpact
Core magnetic fluxMay increase when frequency decreases
No-load currentMay increase
Core temperature riseIncreases
Operating efficiencyDecreases

Therefore, when purchasing dry-type transformers for overseas projects, the following parameters must be confirmed:

  • System frequency
  • Voltage level
  • Ambient temperature
  • Installation altitude
  • Protection degree (IP rating)

II. Rated Voltage and Voltage Ratio

1.Rated Voltage

The rated voltage refers to the designed operating voltage of the transformer’s primary and secondary windings.

Common voltage combinations for dry-type transformers:

High Voltage SideLow Voltage SideApplication
10kV0.4kVIndustrial plants, commercial buildings
20kV0.4kVUrban distribution systems
35kV0.4kVLarge industrial projects

Example: SCB13-2000/10 Dry-Type Transformer

ParameterValue
ModelSCB13-2000/10
Rated Capacity2000kVA
High Voltage Side10kV
Low Voltage Side0.4kV
Frequency50Hz
Vector GroupDyn11
Cooling MethodAN/AF

This transformer is designed for 10kV industrial distribution systems. After voltage reduction, it supplies power to low-voltage electrical equipment.

2.Voltage Ratio

The transformer voltage ratio represents the relationship between the primary-side voltage and the secondary-side voltage.

Calculation formula:

U₁/U₂ = N₁/N₂

Where:

  • U₁: Primary-side voltage
  • U₂: Secondary-side voltage
  • N₁: Number of turns in the primary winding
  • N₂: Number of turns in the secondary winding

Common Step-Down Applications:

Input VoltageOutput VoltageApplication
35kV0.4kVLarge industrial plants
10kV0.4kVGeneral industrial power distribution
6kV0.4kVCertain mining and industrial systems

The transformer voltage level must be properly matched with the power system.

If the equipment operates continuously at a voltage higher than its designed value, it may cause:

  • Increased core magnetic flux density
  • Higher no-load losses
  • Increased temperature rise
  • Accelerated insulation aging

Proper voltage matching is therefore essential to ensure transformer efficiency, reliability, and service life.

III. Rated Capacity

Rated capacity is one of the most important selection parameters for dry-type transformers, with the unit expressed in kVA.

It represents the maximum apparent power that a transformer can continuously deliver under specified operating conditions.

Calculation formula:

S = √3 × U × I

Where:

  • S: Rated capacity
  • U: Rated voltage
  • I: Rated current

Common Capacity Ratings

Capacity RangeApplication
Below 100kVASmall equipment power supply
100–1600kVACommercial buildings and general industrial applications
1600–3150kVALarge industrial plants and data centers
Above 3150kVALarge industrial projects and renewable energy projects

Capacity Selection Principles

In actual engineering projects, transformer capacity should not be selected only based on the current load. The following factors should also be considered:

  • Maximum present load
  • Future load growth
  • Motor starting current
  • Overall operating economy

Generally, it is recommended that the transformer’s long-term operating load rate be maintained at approximately 70%–85%.

Low load operation:

  • Higher initial investment
  • Higher proportion of no-load losses

High load operation:

  • Increased temperature rise
  • Accelerated insulation aging
  • Reduced service life

Engineering Application Case

A manufacturing project adopted a 10kV dry-type transformer power supply system.

Equipment Configuration

EquipmentQuantityParameters
Epoxy resin cast dry-type transformer4 units2500kVA, 10/0.4kV
Epoxy resin cast dry-type transformer6 units2000kVA, 10/0.4kV
Epoxy resin cast dry-type transformer2 units1000kVA, 10/0.4kV

Main Applications

  • Power supply for production equipment
  • Process system power supply
  • HVAC and ventilation systems
  • Auxiliary power facilities

The equipment adopts Class H insulation materials and is designed according to Class F temperature rise limits, improving long-term operational reliability and extending service life.

IV. Winding Connection Group Designation

The vector group designation is used to indicate the connection method of the high-voltage and low-voltage windings of a dry-type transformer, as well as the phase displacement relationship between the two sides.

In engineering applications, the vector group not only affects the operating mode of the power supply system, but also directly influences parallel operation of transformers, harmonic control, and coordination with protection devices.

1. Composition of Vector Group Designation

The transformer vector group is generally represented by a combination of letters and numbers.

Example: Dyn11

SymbolMeaning
DHigh-voltage winding connected in delta (Δ)
yLow-voltage winding connected in star (Y)
nNeutral point of the low-voltage side is brought out
11Phase displacement of 30° between high-voltage and low-voltage sides

2. Common Connection Types

Vector GroupConnection MethodApplication
Yyn0High-voltage star connection, low-voltage star connectionSmall-capacity distribution systems
Dyn11High-voltage delta connection, low-voltage star connection with neutral pointMost widely used in industrial and commercial power distribution
Yd11High-voltage star connection, low-voltage delta connectionHigh-voltage substations
Dd0Both high-voltage and low-voltage windings connected in deltaSpecial industrial applications

3. Why Is Dyn11 Widely Used?

In current 10kV/0.4kV distribution systems, Dyn11 is the most commonly used transformer vector group.

The main reasons include:

(1) Improved Third Harmonic Suppression

The high-voltage side adopts a delta connection, which provides a closed path for third harmonic currents, reducing voltage waveform distortion and improving power quality.

(2) Better Adaptability to Unbalanced Loads

Industrial plants and commercial buildings contain a large number of single-phase loads, such as:

  • Lighting systems
  • Office equipment
  • Control systems

The Dyn11 configuration provides better tolerance to three-phase load imbalance and improves system stability.

(3) Improved Low-Voltage Side Grounding Protection

The neutral point of the low-voltage side is brought out, allowing the formation of a reliable grounding system and improving the operating reliability of protection devices.

V. Impedance Voltage and Load Loss

1. Impedance Voltage

Impedance voltage (Uk%) is one of the most important performance parameters of a transformer.

It represents the percentage of rated primary voltage that must be applied to the transformer primary side when the secondary side is short-circuited, in order to produce the rated current.

Calculation formula:Uk%=UzU1×100%Uk\%= \frac{U_z}{U_1}\times100\%Uk%=U1​Uz​​×100%

Where:

  • Uz: Short-circuit test voltage
  • U1: Rated primary voltage

2. Impact of Impedance Voltage on Operation

The impedance voltage directly affects:

  • Short-circuit current
  • Voltage regulation
  • System stability
Impedance VoltageAdvantagesDisadvantages
Lower impedance voltageSmaller voltage drop, higher efficiencyHigher short-circuit current
Higher impedance voltageBetter limitation of short-circuit currentLarger voltage drop

Typical Impedance Voltage of Dry-Type Transformers

CapacityTypical Impedance Voltage
Below 630kVA4%-6%
800-2500kVA6%-8%
Above 3150kVA8%-10%

Example: SCB13-2000/10 Dry-Type Transformer

ParameterValue
Rated Capacity2000kVA
Impedance Voltage6%
Vector GroupDyn11
Voltage Rating10/0.4kV

3. Load Loss

Load loss is mainly caused by the resistance of the transformer windings, and is also known as copper loss.

Calculation formula:Pcu=I2RP_{cu}=I^2RPcu​=I2R

When the transformer load increases, the winding current increases, causing copper loss to rise rapidly.

For example, for the same 2000kVA dry-type transformer:

  • At 50% load operation:
    • Lower copper loss
    • Lower temperature rise
  • At 100% load operation:
    • Significantly increased copper loss
    • Higher winding temperature

Therefore, during long-term operation, the transformer load rate should be properly controlled to maintain efficiency and extend service life.

3

3. Load Loss

Load loss is mainly caused by the resistance of the transformer windings, and is also known as copper loss.

Calculation formula:Pcu=I2RP_{cu}=I^2RPcu​=I2R

Where:

  • Pcu: Load loss (copper loss)
  • I: Winding current
  • R: Winding resistance

As the transformer load increases, the winding current increases, causing copper loss to rise rapidly.

For example, for the same 2000kVA dry-type transformer:

  • Operating at 50% load:
    Copper loss is relatively low; temperature rise is limited.
  • Operating at 100% load:
    Copper loss increases significantly; winding temperature rises accordingly.

Therefore, during long-term operation, the transformer load rate should be properly controlled to ensure reliable performance, reduce energy losses, and extend the service life of the insulation system.

VI. Temperature Rise and Cooling Methods

1. Importance of Temperature Rise

Unlike oil-immersed transformers, dry-type transformers do not have an oil circulation cooling system. Therefore, winding temperature control mainly relies on:

  • Ambient air circulation
  • Winding structure design
  • Forced cooling by fans

The main heat sources generated during transformer operation include:

Heat SourceCause
Core lossHysteresis loss and eddy current loss
Winding lossHeat generated by winding resistance
Structural component lossAdditional losses caused by leakage flux

2. Insulation Class

Common insulation classes used in dry-type transformers:

Insulation ClassMaximum Allowable TemperatureApplication
Class B130℃General-purpose equipment
Class F155℃Mainstream dry-type transformers
Class H180℃High-temperature environments

Currently, epoxy resin cast dry-type transformers used in industrial projects typically adopt:

Class H insulation materials + Class F temperature rise design

This design approach helps reduce actual operating temperature, improve thermal performance, and extend the service life of the transformer.

3. Cooling Methods

The cooling methods of dry-type transformers are mainly divided into:

Cooling MethodDescriptionApplication
ANNatural air coolingSmall-capacity dry-type transformers
AFForced air coolingLarge-capacity dry-type transformers

Example: SCB13-2000/10 dry-type transformer

  • Normal operation: AN natural air cooling
  • High-load operation: AF fan cooling activated to improve heat dissipation capability

VII. Insulation System of Dry-Type Transformers

The operational stability and reliability of dry-type transformers largely depend on the insulation material system.

The most widely used insulation method is:

Epoxy Resin Cast Insulation

Its main characteristics include:

  • Excellent moisture resistance
  • High mechanical strength
  • Low partial discharge level
  • Good adaptability to industrial environments

Main Insulation Materials

MaterialFunction
Epoxy resinHigh-voltage winding insulation encapsulation
Glass fiberImproves mechanical strength
DMD insulation materialLayer insulation between windings
Polyester filmTurn-to-turn insulation
Mica materialImproves heat resistance performance

Application Requirements for High-Temperature Environments in the Middle East

2

Application Requirements for Dry-Type Transformers in High-Temperature Environments

In regions such as Saudi Arabia and the United Arab Emirates, dry-type transformers typically need to meet the following requirements:

ItemRequirement
Ambient Temperature50℃
Protection RatingIP23/IP54
Insulation ClassClass F / Class H
Corrosion ProtectionEnhanced anti-corrosion treatment
Design StandardIEC 60076

In high-temperature environments, insufficient heat dissipation capability may lead to:

  • Increased winding temperature rise
  • Accelerated insulation aging
  • Reduced service life

Therefore, dry-type transformers used in Middle Eastern industrial projects are usually designed with increased temperature-rise margins.

VIII. Typical Engineering Application Case of Dry-Type Transformers

1. Jubail Industrial City Power Workshop Project, Saudi Arabia

Jubail Industrial City, located in Saudi Arabia’s Eastern Province, is one of the most important petrochemical and industrial manufacturing bases in the Middle East.

The region is continuously exposed to harsh environmental conditions, including:

  • High temperature
  • High humidity
  • Salt mist corrosion
  • Dust and sand

These conditions place high requirements on the environmental adaptability and reliability of electrical equipment.

The project power workshop adopted dry-type transformers as the main power distribution equipment, providing stable power supply for:

  • Production equipment
  • Auxiliary power systems
  • Plant low-voltage distribution systems

Project Configuration

Equipment TypeQuantityMain Parameters
Epoxy resin cast dry-type transformer12 units10kV/0.4kV
Packaged substation10 units10kV/0.4kV
Dry-type transformer capacity2500kVA, 2000kVA, 1000kVA

Main Equipment Parameters

2500kVA Dry-Type Transformer

ParameterTechnical Specification
ModelSCB13-2500/10
Rated Capacity2500kVA
High Voltage Side10kV
Low Voltage Side0.4kV
Frequency50Hz
Vector GroupDyn11
Insulation MethodEpoxy resin cast insulation
Insulation ClassClass H
Cooling MethodAN/AF
Protection RatingIP23/IP54

2000kVA Dry-Type Transformer

ParameterTechnical Specification
ModelSCB13-2000/10
Rated Capacity2000kVA
High Voltage Side10kV
Low Voltage Side0.4kV
Rated Frequency50Hz
Vector GroupDyn11
Impedance Voltage6%
Cooling MethodAN/AF
Insulation MaterialEpoxy Resin

1000kVA Dry-Type Transformer

ParameterTechnical Specification
ModelSCB13-1000/10
Rated Capacity1000kVA
High Voltage Side10kV
Low Voltage Side0.4kV
Frequency50Hz
Vector GroupDyn11
Cooling MethodAN
Insulation ClassClass F / Class H

Project Design Features

Considering the operating environment in Jubail, the key design considerations include:

1. High-Temperature Adaptability

The equipment is designed for a 50℃ ambient temperature, improving winding heat dissipation capability.

Main measures include:

  • Increasing thermal design margin
  • Optimizing winding structure
  • Installing forced air cooling systems

2. Salt Mist Corrosion Protection

Coastal areas contain high concentrations of chloride ions in the air, which can accelerate corrosion of metal components.

The equipment adopts:

  • Anti-corrosion coatings
  • Stainless steel fasteners
  • Enhanced surface treatment

3. Dust Protection Design

Industrial areas often contain large amounts of dust, which may affect insulation performance if it enters the equipment.

Protection measures include:

  • IP23/IP54 protection rating
  • Sealed enclosure structure
  • Optimized ventilation and filtration design

IX. Summary of Key Selection Parameters for Dry-Type Transformers

In practical projects, the main parameters considered for dry-type transformer selection include:

ParameterDescriptionSelection Requirement
Rated CapacityOutput capabilitySelected according to maximum load demand
Rated VoltageVoltage levelMust match the power system
FrequencySystem frequency50Hz or 60Hz
Vector GroupWinding connection methodDyn11 commonly used
Impedance VoltageShort-circuit impedanceDetermined according to system requirements
No-load LossCore lossAffects long-term operating cost
Load LossWinding lossAffects full-load efficiency
Temperature RiseHeat generation levelAffects insulation life
Insulation ClassThermal endurance capabilityClass F/H commonly used
Cooling MethodHeat dissipation methodAN/AF

X. Operation and Maintenance Requirements for Dry-Type Transformers

Although dry-type transformers require less maintenance compared with oil-immersed transformers, regular inspections are still necessary during long-term operation.

Main Inspection Items

Inspection ItemPurpose
Temperature MonitoringDetermine whether winding temperature rise is normal
Load MonitoringCheck whether the equipment is overloaded
Insulation TestingEvaluate insulation aging condition
Sound InspectionDetect abnormal conditions in the core and structure
Visual InspectionCheck dust accumulation, cracks, and corrosion

Common Operating Problems

1. Excessive Temperature Rise

Possible causes:

  • Long-term overload operation
  • Insufficient ventilation
  • Cooling fan failure
  • Excessively high ambient temperature

Corrective measures:

  • Reduce load
  • Check the cooling system
  • Clean ventilation channels

2. Increased Partial Discharge

Possible causes:

  • Winding contamination
  • Moisture absorption in insulation
  • Cracks in epoxy resin insulation

Corrective measures:

  • Perform regular partial discharge testing
  • Inspect insulation condition
  • Keep the transformer clean and dry

About ZISHENG ELECTRICAL

Zisheng are a professional 19+ years manufacturer in producing Oil-Immersed Transformers, Compact Substation, Pad Mounted Transformers, Pole Mounted Transformers and Dry Type Transformers. We own the certificates of ISO/CE/IEC 60076 and TUV Rheinland.
Transformers undergo rigorous FAT and type testing, support voltage/capacity customization. Welcome to consult for Catalog and Product. you can contact us at email [email protected].

+86-191-3128-5373 +86-191-3128-5373 [email protected]